SafeGuard Fire Solutions
Excellence in Safety Compliance
Ref: SFS-2026-001
Date: May 10, 2026

Fire Safety & Compliance Audit

Site Evidence Site Report

Prepared for
Global Logistics Hub
West Side Warehouse, London

Prepared by
Sarah Jenkins
Senior Fire Consultant
Ref: SFS-2026-001 May 10, 2026
SAFEGUARD FIRE SOLUTIONS
Audit Overview

Global Logistics Hub

West Side Warehouse, Terminal 4 Industrial Estate, London
Reviewed
12
Findings
3
Critical
1
Compliance
85%
Inspector
Sarah Jenkins (IFE Accredited)
Audit Type
Annual Compliance Review
Standards
BS 5839-1, BS 5266-1, BS 5306-3

Executive Summary

A comprehensive fire safety audit was conducted at the West Side Warehouse facility. Overall, the facility maintains a high standard of compliance. Key findings relate to the compartmentalization integrity in the main loading bay and minor signage updates required in the mezzanine office area.

Scope

The inspection covered all accessible areas including the warehouse floor, office spaces, and external fire assembly points. Focus was placed on fire detection systems, portable firefighting equipment, and escape route integrity.

Ref: SFS-2026-001
SAFEGUARD FIRE SOLUTIONS
Item 01

Water Fire Extinguisher (9L)

Location
Main Hallway A
Status
Compliant
Last Service
Jan 2026
Priority
Low
Fire Extinguisher
Observation Photo 1.1. Extinguisher is correctly mounted, unobstructed, and clearly signed in accordance with BS 5306.
Ref: SFS-2026-001
SAFEGUARD FIRE SOLUTIONS
Item 02

Main Entrance Fire Door

Location
Warehouse Entrance
Status
Non-Compliant
Assigned To
Maintenance Dept
Due Date
May 17, 2026
Damaged Fire Door
Observation Photo 2.1. Excessive gap (>4mm) between door leaf and frame at the hinge side. Intumescent strips are partially detached.
Finding: Compartmentalization Breach

The fire door fails to provide the required 30-minute fire resistance due to the excessive gap and degraded smoke seals. This could allow smoke and fire to transition between zones rapidly.

Recommendation:

Re-hang door to reduce gaps to within 2-4mm and replace all intumescent/smoke seals immediately.

Ref: SFS-2026-001
SAFEGUARD FIRE SOLUTIONS
Item 03

Emergency Exit Signage

Location
Loading Bay Exit
Status
Compliant
Battery Test
Pass
Priority
Low
Emergency Exit Sign
Observation Photo 3.1. Internally illuminated exit sign is fully operational. Durations test confirmed 3-hour autonomy.
Ref: SFS-2026-001
SAFEGUARD FIRE SOLUTIONS
Report Close

Conclusions

Closing Statement

The West Side Warehouse facility demonstrates a proactive approach to fire safety. While the majority of life safety systems are in good working order, the issues identified in this report—specifically the fire door integrity—must be addressed with high priority to maintain the building's fire strategy.

A follow-up inspection is recommended within 30 days of the remedial works being completed to verify compliance.

Issued By

Sarah Jenkins Signature
Sarah Jenkins
Senior Fire Consultant sarah.j@safeguardfire.com Signed: May 10, 2026